| Probable Causes | Solutions |
|---|---|
| Power Supply not connected to switchboard | Connect Power Supply to the Incomer Breaker |
| Control MCBs for Indication Ckt. are off or Control Fuses are blown off | Switch "ON" the MCBs or replace Control Fuse Links whichever is applicable |
| Indicating Lamps are faulty | Replace Indicating Lamps |
| No Control Supply Available | Check for rated Control Supply to the switchboard at the terminals provided as per wiring drawing. |
| Probable Causes | Solutions |
|---|---|
| Closing on Short Circuit | Remove the fault after detection and than close the Circuit Breaker after inspection of circuit breaker condition |
| ACB is not completely in Service Position | Check whether ACB spring is charged* |
| Check whether U/V Release is picked up | |
| Check for any Mechanical or Electrical Interlocking | |
| Check whether Trip command is issued by any Feeder Protection Relay/Device & resolve. | |
| Reset Button Signalling a Fault Trip has not been reset | Remove the fault after detection and than close the Circuit Breaker after inspection of circuit breaker condition |
| No Control Supply Available* | Connect rated Control Supply to the switchboard at the terminals provided as per wiring drawing. |
| Control MCB is "Off"* | Switch "ON" the Control MCBs |
| Selection for Local Mode is not done* | Select Local Mode |
| Closing command not executed by Closing Coil | Check the voltage and the supply circuit, if problem persists replace the Closing Coil |
| Interlocking Ckt. Not working | Check for proper control voltage/Micro PLC UPS Supply. If problem persists contact STANDARD CONTROL PANEL PVT. LTD. Mobile: +91-98764-00718, +91-99884-20003 |
| Plug-in terminals provided at Transport Section not connected | Connect the Plug-in terminals |
| Breaker Control Switch Faulty | Replace faulty Breaker Control Switch. |
| Probable Causes | Solutions |
|---|---|
| Opening command not executed byTripping Coil | Check the voltage and the supply circuit, if problem persists replace the Tripping Coil |
| Welded contacts of the Circuit Brekers | Contact STANDARD CONTROL PANEL PVT. LTD. Mobile: +91-98764-00718, +91-99884-20003 |
| No Control Supply Available | Check for rated Control Supply to the switchboard at the terminals provided as per wiring drawing. |
| Breaker Control Switch Faulty | Replace faulty Breaker Control Switch. |
| Probable Causes | Solutions |
|---|---|
| Circuit Breaker in Closed/On condition | Open the Circuit Breaker |
| Probable Causes | Solutions |
|---|---|
| Presence of any Rack In/Out Interocking | Follow correct Interlocking sequence |
| Probable Causes | Solutions |
|---|---|
| U/V Release supply too low | Check the voltage and the supply circuit, if problem persists replace the U/V Release |
| Wrong operation sequence done manually | Follow the correct operation sequence and restore supply |
| Tripping on Fault (i.e. Overload, Shortcircuit, Earthfault) | Remove the fault after detection and than close the Circuit Breaker after inspection of circuit breaker condition |
| Probable Causes | Solutions |
|---|---|
| Feeder SCPD i.e.(MCCB, SDFU, MCB) is in 'OFF' condition | Switch'ON' the Feeder SCPD |
| Thermal O/L relay is in Trip Conditon | Reset the O/L relay by means of reset push button on the relay |
| Start push button is not working properly | Check start push button element for proper working |
| Local Mode selection not done | Select Local Mode through selector switch provided on Feeder Door |
| Any interlocking is preventing the Starter Operation | Check for proper operating seqence. |
| Probable Causes | Solutions |
|---|---|
| Primarly Check for any probable cause as covered under Starter Operation Locally. | Resolve the problem as suggested above |
| Remote mode selection not done | Select Remote Mode through selector switch provided on Feeder Door |
| Any wiring fault for remote close command | Check for Fault and resolve. |
| Probable Causes | Solutions |
|---|---|
| No Control Supply Available | Connect rated Control Supply to the switchboard at the terminals provided as per wiring drawing. |
| Control MCB is "Off" | Switch "ON" the Control MCBs |
| Probable Causes | Solutions |
|---|---|
| No Power Supply Available | Connect Power Supply to the Feeder |
| Control MCBs for PT Ckt. are off or Control Fuses are blown off | Switch "ON" the MCBs or replace Control Fuse Links whichever is applicable |
| Probable Causes | Solutions |
|---|---|
| CT shorting terminals provided in Metering Feeder are still short | Open the shorting link by loosening and sliding down the shorting link |
| No load on the Feeder | Can be checked after putting some load on the feeder. |
| Probable Causes | Solutions |
|---|---|
| SCPD (i.e. MCCBs, SDFU) for the Capacitor Bank Feeder is in 'OFF' condition | Switch 'ON' the SCPD for capacitor bank feeder |
| C.T.shorting link is not open at Trf. End. | Open the C.T. shorting link |
| Auto' selection not done for Capacitor Bank Feeders | Select 'Auto' mode for Feeders by selector switch provided on the feeder door |
| APFC Relay not in 'Auto' mode. | Put the relay in 'Auto' mode. Refer the Relay User Manual |
| Sensing current to the relay is too low. | Opt for a suitable rating Fixed Capacitor Bank. Consult STANDARD CONTROL PANEL PVT. LTD. Mobile: +91-98764-00718, +91-99884-20003 |
| Capacitor Bank are faulty and rejected by APFC Relay | Replace Capacitor Bank. Consult STANDARD CONTROL PANEL PVT. LTD. Mobile: +91-98764-00718, +91-99884-20003 |
| Pre programmed parameters disturbed at site | Check for current programmed parameters and correct if required or cont. STANDARD CONTROL PANEL PVT. LTD. Mobile: +91-98764-00718, +91-99884-20003 |
| Probable Causes | Solutions |
|---|---|
| DG is not started after Set Time Delay | Check for Released Emergency Push Button, key in 'ON' condition. |
| No Control Supply Available | Check for rated Control Supply to the switchboard at the terminals provided as per wiring drawing. |
| Start Command Not Executed by DG Set | Contact respective DG Service Centre |
| D.G. set is not in Remote mode | Put the D.G. in Remote mode by D.G. controller or cont to D.G. vendor |
| AMF Relay not in 'Auto' mode. | Put the relay in 'Auto' mode. Refer the Relay User Manual |
| Fault Signalled by relay | Attend and resolve the fault. If the problem persist call STANDARD CONTROL PANEL PVT. LTD. Mobile: +91-98764-00718, +91-99884-20003 |